Equipment
Cleanroom Equipment
OverviewCleanroom Equipment
Overview
- Cleanroom systems
- GMP systems
- HACCP systems
Cleanroom equipment filters the air entering a clean area, keeps dust from coming in with people and materials, and holds room pressure, temperature and humidity. SAMYOUNG ENG registered its air-handling equipment factory in 2006 and has carried out cleanroom equipment work from air shower and pass box supply to clean booth fabrication and installation and HEPA filter replacement.
Scope of WorkWhat we deliver
Scope of work
01Air Shower
Removes dust from people or items with high-speed clean air before entry
02Pass Box
Installed in a cleanroom wall to transfer small items into the room
03Clean Booth
Creates a local clean space using air supplied through a fan filter unit
04Fan Filter Unit
A unit with a fan and filter that filters air
Cleanroom componentsCleanroom components
Cleanroom components
A cleanroom controls airborne particle concentrations and minimises dust generation, entry and retention.
Environmental conditions such as temperature, humidity, airflow and pressure are maintained to meet requirements.
Cleanroom equipment

What each component does
- 01Fan Filter Unit
A unit with a fan and filter that filters air
- 02HEPA Filter Unit
A unit with a filter that filters air
- 03Clean Booth
Creates a local clean space using air supplied through a fan filter unit
- 04Pass Box
Installed in a cleanroom wall to transfer small items into the room
- 05Air Shower
Removes dust from people or items with high-speed clean air before entry
- 06Relief Damper
Maintains cleanroom differential pressure
- 07Condensing Unit
A condensing assembly with a built-in condenser and compressor
- 08Air Handling Unit
Draws in air and provides air purification, cooling, dehumidification, heating and humidification
- 09Clean Locker
Stores used cleanroom clothing, removes dust from its exterior and prevents dust adhesion
View as table
| Component | Function |
|---|---|
| Fan Filter Unit | A unit with a fan and filter that filters air |
| HEPA Filter Unit | A unit with a filter that filters air |
| Clean Booth | Creates a local clean space using air supplied through a fan filter unit |
| Pass Box | Installed in a cleanroom wall to transfer small items into the room |
| Air Shower | Removes dust from people or items with high-speed clean air before entry |
| Relief Damper | Maintains cleanroom differential pressure |
| Condensing Unit | A condensing assembly with a built-in condenser and compressor |
| Air Handling Unit | Draws in air and provides air purification, cooling, dehumidification, heating and humidification |
| Clean Locker | Stores used cleanroom clothing, removes dust from its exterior and prevents dust adhesion |
Choosing cleanroom equipmentChoosing cleanroom equipment
Choosing cleanroom equipment
When to use each cleanroom device and what to check when choosing it. Performance figures for each device, such as nozzle velocity and filter efficiency, come from the manufacturer's specifications.
Choosing cleanroom equipment
- Air ShowerUse it when
Operators need to remove dust from their bodies and clothing before entering the clean area after gowning
Check when choosing- Separate personnel and material entries where possible (gowning room and air shower for people, pass box for materials).
- Both doors must not open at the same time: interlocks for airlocks leading to Grades A and B of a sterile-medicines facility, at least a visual and/or audible warning for airlocks leading to Grades C and D.
- In sterile-medicines facilities, the final stage of an airlock must match, at rest, the grade of the room it leads to.
- Pass BoxUse it when
Small items have to pass through the wall into the clean area without a person entering
Check when choosing- Decide whether the box must be flushed with filtered air to protect the higher-grade side.
- The doors must not open at the same time (whether to use an interlock is a design choice).
- Only items on an approved list, validated for the transfer process, go into Grades A and B.
- Clean BoothUse it when
Only a specific work zone or bench, not the whole room, needs to be made locally clean with filtered air
Check when choosing- Decide the required cleanliness and airflow pattern first (unidirectional airflow for Grade A sterile manufacture: 0.36–0.54m/s at the working position, guidance value).
- The installation must allow filter integrity testing and airflow volume measurement (requalification items).
- PanelsUse it when
Walls, ceilings and partitions divide the clean area and keep out external contamination
Check when choosing- Choose the panel material and thickness for the cleanliness grade and process of the space.
- Seal panel joints and moulding connections, for example with silicone, to keep the enclosure airtight.
View as table
| Device | Use it when | Check when choosing |
|---|---|---|
| Air Shower | Operators need to remove dust from their bodies and clothing before entering the clean area after gowning | Separate personnel and material entries where possible (gowning room and air shower for people, pass box for materials). Both doors must not open at the same time: interlocks for airlocks leading to Grades A and B of a sterile-medicines facility, at least a visual and/or audible warning for airlocks leading to Grades C and D. In sterile-medicines facilities, the final stage of an airlock must match, at rest, the grade of the room it leads to. |
| Pass Box | Small items have to pass through the wall into the clean area without a person entering | Decide whether the box must be flushed with filtered air to protect the higher-grade side. The doors must not open at the same time (whether to use an interlock is a design choice). Only items on an approved list, validated for the transfer process, go into Grades A and B. |
| Clean Booth | Only a specific work zone or bench, not the whole room, needs to be made locally clean with filtered air | Decide the required cleanliness and airflow pattern first (unidirectional airflow for Grade A sterile manufacture: 0.36–0.54m/s at the working position, guidance value). The installation must allow filter integrity testing and airflow volume measurement (requalification items). |
| Panels | Walls, ceilings and partitions divide the clean area and keep out external contamination | Choose the panel material and thickness for the cleanliness grade and process of the space. Seal panel joints and moulding connections, for example with silicone, to keep the enclosure airtight. |
- Basis: EU GMP Annex 1 (2022) sections 4.10, 4.12, 4.13, 4.30 and 4.32; MFDS GMP regulation Annex 1, section 4. Interlock, pressure and airflow requirements are sterile-medicines rules; other facilities set them by process risk.
- Track record (2025 company profile): air shower and pass box supply (2006), panel and air shower installation (2006), injectables clean booth expansion (2025), clean booth installation (2014) and cleanroom panel installation (2020), among others.
Equipment projectsEquipment projects
Equipment projects
SAMYOUNG ENG registered its air-handling equipment factory in 2006 and has carried out cleanroom equipment work from air shower and pass box supply to clean booth fabrication and installation and HEPA filter replacement.
Projects from the 2025 company profile track record in which we supplied, fabricated, installed or replaced cleanroom equipment.
View as table
| Year | Project |
|---|---|
| 2025 | Injectables clean booth expansion |
| 2025 | 6th-floor cleanroom HEPA filter replacement and PAO test |
| 2024 | Weighing booth upgrade in the main building weighing room |
| 2022 | Clean booth relocation and installation |
| 2021 | TOC booth fabrication and installation |
| 2020 | Cleanroom equipment installation in an inorganic analysis laboratory |
| 2019 | Clean booth for the inorganic analysis laboratory of the National Environmental Specimen Bank |
| 2017 | Clean booth fabrication and installation |
| 2014 | Clean booth installation at the Ansan plant |
| 2013 | Clean booth installation in production building G at the Ansan plant |
| 2012 | Clean booth installation in the aseptic building at the Ansan plant |
| 2010 | Cleanroom equipment installation |
| 2009 | Cleanroom equipment fabrication and installation for an injection-moulding room |
| 2007 | Clean booth and dust collector installation in the Ansan plant ampicillin store |
| 2006 | Air shower and pass box supply |
| 2006 | Panel and air shower installation |
- Source: 2025 company profile track record. Performance figures for each device come from the manufacturer's specifications.