HVAC TAB Procedure
TAB tests, adjusts and balances HVAC flows and conditions. Follow the sequence from preparation to measurement and reporting.
Measured ItemsWhat TAB measures
| Item | Measurements | Key conditions |
|---|---|---|
| Airflow and velocity | AHU, duct and supply/return/exhaust terminal flows and distribution | Operating mode, fan speed, damper position and filter condition |
| Static pressure | Static pressure and pressure losses at fans, ducts and filters | Tap location, airflow and instrument range |
| Differential pressure | Room differentials and intended airflow direction | Door state, leakage and supply/exhaust combinations |
| Temperature and humidity | Supply/return/room temperature and relative humidity | Outdoor, equipment and occupancy loads, stabilisation time and measurement positions |
| Water flow and equipment operation | Applicable chilled/hot-water flows, pressure and pump/fan operation | Apply to systems included in the agreed scope |
Tolerances come from the contract specification, design documents and approved test plan. Do not apply one ±% to every item or change acceptance criteria after measuring.
ProcedureTAB procedure
| Stage | Work | Records and results |
|---|---|---|
| 1. Design review and plan | Define systems, design flows/pressures, operating modes, tolerances, test points and instruments | TAB plan, design-value register and measurement forms |
| 2. Installation readiness | Check ducts, pipes, filters, dampers, valves, sensors and access; verify rotation and controls | Readiness checklist and resolved/open items |
| 3. Initial measurements | Measure system, branch and terminal baselines under design operating conditions | Raw pre-adjustment flow, pressure and temperature/humidity readings |
| 4. Adjust and balance | Adjust fans/pumps, branches and terminals in sequence and remeasure interactions | Final positions, speeds, set points and repeat readings |
| 5. Final verification and report | Check deviations by mode, room pressure/temperature/humidity and agreed alarm/changeover functions | Final report, marked-up drawings, deviations and outstanding items |
DeliverablesTAB report contents
Record system and equipment IDs, drawing/specification revisions, design/measured values, deviations and conclusions, instrument IDs and calibration validity, measurement positions/time/operating conditions and before/after adjustment readings. Trace any shortfall through its cause, action and remeasurement.
Hand over final damper/valve positions and control settings on drawings and schedules. Identify the zones affected by changes and define the checks needed after extensions, filter replacement or operating-mode changes.
IQ / OQHow TAB relates to IQ and OQ
TAB commissions and measures the design operating points; it does not itself complete GMP qualification. IQ checks installation, materials, calibration and documentation against the approved design; OQ verifies operating ranges, alarms and functions against protocol criteria.
To use TAB results as qualification evidence, review methods, instruments, criteria and raw-data traceability and link them to an approved protocol before testing. Document the required tests, deviations and retesting. (EU GMP Annex 15, section 3)
SAMYOUNG ENG supports IQ/OQ documentation and testing and TAB for GMP facilities, using its own airflow meters, anemometers, a particle counter, digital temperature/humidity meters, an electronic flowmeter and a temperature recorder.
FAQFrequently asked questions
Frequently asked questions
What does TAB stand for?
Testing, adjusting and balancing. It brings HVAC air/water flows and environmental conditions to the design requirements and documents the final measurements.
Does completing TAB finish OQ?
No. TAB is commissioning; OQ documents tests of operating ranges, functions and alarms under an approved protocol. Suitable TAB raw data may be used as evidence after review and approval.
Is TAB needed after filter replacement?
Changed filter resistance can affect airflow and room pressure. Define remeasurement and rebalancing from the change impact and plan any required requalification for GMP facilities.